Inverse Time Over Current (TOC/IDMT) Relay Trip Time Calculator
This calculator computes the protection trip time according to IEC 60255 and IEEE C37.112-1996 protection curves.
Key Parameters:
- Trip Curve: Select from the standard IEC and IEEE curves.
- Relay Pickup Current (A): The relay's pickup set point current, denoted as Is
- Fault Current (A): The anticipated fault current during short circuits.
- TMS (IEC) or TD (IEEE) Setting: Time settings for the relay:
- IEC: Time Multiplier Setting (TMS).
- IEEE: Time Dial (TD) or Time Dial Multiplier (TDM).
What is Inverse Time Overcurrent (TOC)?
TOC (or IDMT - Inverse Definite Minimum Time) ensures trip times are inversely proportional to the fault current, providing faster response for higher fault currents.
What is IDMT?
IDMT (Inverse Definite Minimum Time) is a time-current characteristic where higher fault currents result in quicker tripping of the relay.
IEC 60255 IDMT Trip Curves
The trip time for IEC 60255 can be calculated using the formula:
\[t(I) = TMS \left(\frac{k}{\left(\left(\frac{I}{I_s}\right)^\alpha - 1\right)}\right)\]Where:
- \(I_s\): Relay's current setting.
- \(I\): Actual measured current.
- \(k\), \(\alpha\): Curve constants (see table below).
IEC 60255 Equation Constants
Curve Type | k | α |
---|---|---|
Standard Inverse | 0.140 | 0.020 |
Very Inverse | 13.5 | 1 |
Extremely Inverse | 80 | 2 |
Long Time Standard Inverse | 120 | 1 |
IEEE C37.112-1996 IDMT Trip Curves
For IEEE C37.112-1996 standards, the trip time is given by:
\[t(I) = TD \left(\frac{A}{\left(\left(\frac{I}{I_s}\right)^p - 1\right)} + B\right)\]Where:
- \(I_s\): Relay's current setting.
- \(I\): Actual measured current.
- \(A\), \(B\), and \(p\): Curve constants (see table below).
IEEE C37.112-1996 Equation Constants
Curve Type | A | B | p |
---|---|---|---|
Moderately Inverse | 0.0515 | 0.114 | 0.02 |
Very Inverse | 19.61 | 0.491 | 2 |
Extremely Inverse | 28.2 | 0.1217 | 2.0 |